This system is forced circulation fully automatic thermic fluid heater where thermic fluid is circulated in a closed loop through heater and user equipment circuit where the heat is dissipated to process. The same thermic fluid is re-circulated through heater for heating. The thermic fluid heater gives high temperature up to 300°C using thermic fluid oil at near atmospheric pressure as compared to steam heating which requires 85 Kg/Cm2 pressure.
Parameter | Unit | Model | |||||
RFPL - 400 | RFPL - 600 | RFPL - 1000 | RFPL - 1500 | RFPL - 2000 | |||
Heat Output | Kcal/Hr | 4,00,000 | 6,00,000 | 10,00,000 | 15,00,000 | 20,00,000 | |
Maxfield Outlet Temperature | oC | 300 | |||||
Max. Head at heater Outlet | M/c | 27 | |||||
Efficiency on GCV | With APH+ | % | 75 | ||||
Without APH+ | % | 70 | |||||
Rated fuel consumption | Steam Coal | Kg/hr. | 116 | 175 | 290 | 435 | 580 |
Lignite | Kg/hr. | 150 | 226 | 376 | 564 | 752 | |
Agro-waste | Kg/hr. | 174 | 260 | 433 | 650 | 866 | |
Thermic Fluid Pump Motor | Kw | 7.5 | 9.30 | 11.0 | 18.5 | 30 | |
I.D.Fan Motor | Kw | 3.7 | 5.5 | 9.3 | 11.0 | 15.0 | |
Over fire fan motor | Kw | – | 1.50 | 2.20 | 3.70 | 5.50 | |
Total Load | Kw | 11.20 | 16.30 | 22.50 | 33.20 | 50.70 | |
Expansion Tank Capacity | Liters | 800 | 800 | 1000 | 1000 | 1250 | |
Overall Dimensions | Length | mm | 4600 | 6000 | 7500 | 7800 | 10000 |
Width | mm | 3800 | 4000 | 4500 | 5400 | 6200 |